Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 8, 2020, 09:12 AM
  • H 0580_H 0579 _05082020_022740.mp4

Date
05/08/2020
W/O
828927
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00188
PipeID
P11004
Time
2:12 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7656
Sewer Name
H JOINT OUTFALL H - UNIT 8E
City
BALDWIN PARK
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_828927_TV15172_MAY2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
H 0580
Downstream MH
H 0579
Dir. of Survey
Downstream
Length Surveyed
276 ft.
Total Length
276 ft.
Structural Index
3
Structural Quick
3I2J
Structural Rating
262
O&M Index
2
O&M Quick
4131
O&M Rating
117
Overall Index
2
Overall Quick
Overall Rating
379
Pipe schematic from manhole H 0580 to H 0579
MH: H 0580MH: H 0579downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 05800 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start9.5 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start9.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start10 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"18.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"55.3 ft. OBC - Obstacles Thru Connection, 10 %of cross sectional area, at 01 o'clock55.3 ft. TBD - Tap Break-In Defective, at 12 o'clock, -, , within 8 inches of joint: NO, 6"170.9 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN206.4 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start206.4 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish212.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"220.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"273.4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish273.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE273.4 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish273.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish276 ft. AMH - Downstream Manhole, Survey Ends - H 0579

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    9.5 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    9.5 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Defective, at 12 o'clock, -,  , within 8 inches of joint: NO, 6"

    55.3 ft. - Tap Break-In Defective, at 12 o'clock, -, , within 8 inches of joint: NO, 6"

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    206.4 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    273.4 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (20)

DistanceCodeObservation
276AMHH 0579
0MWL
10TFC
273.4SSS
170.9TBOPEN
206.4SAV
55.3OBC
0AMHH 0580
273.4MGOCOCKROACHES IN MANHOLE
55.3TBD
18.4TFC
0MWM
273.4SAV
206.4SAP
220.3TFC
273.4DAGS
9.5SAP
2DAGS
212.7TFC
9.5SSS

Properties (6)

additional_info
SC411247
custom_field_two
2
customer
LACSD
datetime
2020-05-08T02:12:29-07:00
documentation
PRO PIPE
is_lateral_inspection
false