Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 21, 2020, 05:50 AM
  • 18 0107_18 0106 _05202020_230840.mp4

Date
05/20/2020
W/O
828920
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13927
Time
10:50 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7708
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_828920_TV18177_MAY2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0107
Downstream MH
18 0106
Dir. of Survey
Downstream
Length Surveyed
311.5 ft.
Total Length
311.5 ft.
Structural Index
3
Structural Quick
3O2D
Structural Rating
298
O&M Index
2
O&M Quick
2K00
O&M Rating
122
Overall Index
2
Overall Quick
Overall Rating
420
Pipe schematic from manhole 18 0107 to 18 0106
MH: 18 0107MH: 18 0106downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0 ft. MGO - General Observation - ROACHES @ MH0 ft. AMH - Upstream Manhole, Survey Begins - 18 01070 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start9.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN13.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"42 ft. CM - Crack Multiple, from 07 to 12 o'clock, within 8 inches of joint: YES58 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"61.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"109.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN112.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"162.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN164.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"181.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES187.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start210.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN213.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN215.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start259 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"261.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"309 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish311 ft. MGO - General Observation - ROACHES @ MH311.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish311.5 ft. AMH - Downstream Manhole, Survey Ends - 18 0106311.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish311.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (5)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 07 to 12 o'clock, within 8 inches of joint: YES

    42 ft. - Crack Multiple, from 07 to 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    181.9 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    187.6 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    215.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (29)

DistanceCodeObservation
58TFC
309DAGS
0MWM
2DAGS
109.9TFOPEN
261.9TFC
181.9CL
162.5TFOPEN
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
61.3TFC
213.3TFOPEN
311.5CM
187.6CL
42CM
311.5AMH18 0106
259TFA
215.1CM
210.5TFOPEN
2.1SAV
0MGOROACHES @ MH
0AMH18 0107
164.6TFC
311MGOROACHES @ MH
9.4TFOPEN
0MWL
311.5CL
13.3TFC
311.5SAV
112.8TFC

Properties (6)

additional_info
SC411365
custom_field_two
3
customer
LACSD
datetime
2020-05-20T22:50:38-07:00
documentation
PROPIPE
is_lateral_inspection
false