Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 21, 2020, 07:07 AM
  • 18 0103_18 0102 _05212020_002336.mp4

Date
05/21/2020
W/O
828920
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13923
Time
12:07 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7708
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_828920_TV18177_MAY2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0103
Downstream MH
18 0102
Dir. of Survey
Downstream
Length Surveyed
355.6 ft.
Total Length
355.6 ft.
Structural Index
3
Structural Quick
3M2M
Structural Rating
360
O&M Index
2
O&M Quick
2M00
O&M Rating
140
Overall Index
2
Overall Quick
Overall Rating
500
Pipe schematic from manhole 18 0103 to 18 0102
MH: 18 0103MH: 18 0102downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH0 ft. AMH - Upstream Manhole, Survey Begins - 18 01032 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start12 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN14.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"55.9 ft. CL - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES57.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"60.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"112.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"115.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"163.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN167.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"212.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN214 ft. CM - Crack Multiple, from 07 to 12 o'clock, within 8 inches of joint: YES215.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"261 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"264.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"312.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"316.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"342.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES346.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"349.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"353 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish353 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish355.6 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE355.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish355.6 ft. AMH - Downstream Manhole, Survey Ends - 18 0102355.6 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE

Observation photos (4)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

    55.9 ft. - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 12 o'clock, within 8 inches of joint: YES

    214 ft. - Crack Multiple, from 07 to 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    342.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (32)

DistanceCodeObservation
353SSS
115.2TFC
355.6MGOCONN @ MH 9 O'CLOCK/ACTIVE
349.5TFC
2.1SAV
167.3TFC
342.1CL
355.6SAV
163.6TFOPEN
355.6AMH18 0102
0MWL
14.7TFC
261TFC
312.9TFC
264.4TFC
214CM
353DAGS
55.9CL
0MWM
57.4TF
355.6MGOCONN @ MH 3 O'CLOCK/ACTIVE
112.8TFC
0MGOROACHES @ MH
12TFOPEN
0AMH18 0103
2SSS
346.3TFC
2DAGS
60.6TFC
215.3TFC
316.1TFC
212.6TFOPEN

Properties (6)

additional_info
SC411365
custom_field_two
3
customer
LACSD
datetime
2020-05-21T00:07:00-07:00
documentation
PROPIPE
is_lateral_inspection
false