Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 21, 2020, 10:22 AM
  • 18 0092_18 0091 _05212020_033622.mp4

Date
05/21/2020
W/O
828920
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13911
Time
3:22 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7708
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_828920_TV18177_MAY2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0091
Downstream MH
18 0092
Dir. of Survey
Upstream
Length Surveyed
324.4 ft.
Total Length
324.4 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
7
Pipe schematic from manhole 18 0091 to 18 0092
MH: 18 0091MH: 18 0092upstream0 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 18 009289.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"95.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"222.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"229 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"312.5 ft. IR - Infiltration Runner, from 10 to 11 o'clock, within 8 inches of joint: YES322.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start324.4 ft. AMH - Downstream Manhole, Survey Begins - 18 0091324.4 ft. MWL - Water Level, 40 %of cross sectional area324.4 ft. MWM - Water Mark, 45 %of cross sectional area

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Runner, from 10 to 11 o'clock, within 8 inches of joint: YES

    11.9 ft. - Infiltration Runner, from 10 to 11 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
0AMH18 0091
11.9IR
101.7TFC
324.4SAV
0MWL
2.3SAV
0MWM
95.4TFC
235TFC
324.4AMH18 0092
228.8TFC

Properties (6)

additional_info
SC411365
custom_field_two
3
customer
LACSD
datetime
2020-05-21T03:22:23-07:00
documentation
PROPIPE
is_lateral_inspection
false