Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 21, 2020, 09:20 AM
  • 18 0091_18 0090 _05212020_032203.mp4

Date
05/21/2020
W/O
828920
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13910
Time
2:20 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7708
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_828920_TV18177_MAY2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0090
Downstream MH
18 0091
Dir. of Survey
Upstream
Length Surveyed
348.7 ft.
Total Length
348.7 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
207
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
209
Pipe schematic from manhole 18 0090 to 18 0091
MH: 18 0090MH: 18 0091upstream0 ft. AMH - Upstream Manhole, Survey Ends - 18 00910.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0.7 ft. MGO - General Observation - ROACHES @ MH50.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"56 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"84.3 ft. TBI - Tap Break-In Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 6", 1" - UNKNOWN251.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"346.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start348.7 ft. AMH - Downstream Manhole, Survey Begins - 18 0090348.7 ft. MWL - Water Level, 35 %of cross sectional area348.7 ft. MGO - General Observation - ROACHES @ MH348.7 ft. MWM - Water Mark, 40 %of cross sectional area

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 6", 1" - UNKNOWN

    264.4 ft. - Tap Break-In Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 6", 1" - UNKNOWN

Observations (12)

DistanceCodeObservation
348.7AMH18 0091
97TFC
264.4TBIUNKNOWN
292.7TFC
0AMH18 0090
2.1SAV
348.6SAV
348MGOROACHES @ MH
0MWL
0MGOROACHES @ MH
298.6TFC
0MWM

Properties (6)

additional_info
SC411365
custom_field_two
3
customer
LACSD
datetime
2020-05-21T02:20:06-07:00
documentation
PROPIPE
is_lateral_inspection