Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 21, 2020, 09:27 AM
  • 18 0089_18 0088 _05212020_023919.mp4

Date
05/21/2020
W/O
828920
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13908
Time
2:27 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7708
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_828920_TV18177_MAY2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0089
Downstream MH
18 0088
Dir. of Survey
Downstream
Length Surveyed
351.1 ft.
Total Length
351.1 ft.
Structural Index
3
Structural Quick
3M21
Structural Rating
212
O&M Index
2
O&M Quick
2[00
O&M Rating
278
Overall Index
2
Overall Quick
Overall Rating
490
Pipe schematic from manhole 18 0089 to 18 0088
MH: 18 0089MH: 18 0088downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 00890.1 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start2.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start59.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"160 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"200 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 01 to 05 o'clock, , within 8 inches of joint: YES237 ft. IS - Infiltration Stain, from 02 to 05 o'clock, within 8 inches of joint: YES253.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"270.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES270.4 ft. IS - Infiltration Stain, from 07 to 12 o'clock, within 8 inches of joint: YES349 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish349 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish351.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish351.1 ft. AMH - Downstream Manhole, Survey Ends - 18 0088351.1 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE

Observation photos (4)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Stain, from 02 to 05 o'clock, within 8 inches of joint: YES

    237 ft. - Infiltration Stain, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    270.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Infiltration Stain, from 07 to 12 o'clock, within 8 inches of joint: YES

    270.4 ft. - Infiltration Stain, from 07 to 12 o'clock, within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
349DAE
2DAGS
253.5TFC
270.4CL
237IS
349DAGS
0MWL
59.2TFC
351.1SAV
2DAE
0AMH18 0089
2.3SAV
160TFC
351.1AMH18 0088
351.1MGOCONN @ MH 3 O'CLOCK/ACTIVE
270.4IS
200DAE
0.1MWM

Properties (6)

additional_info
SC411365
custom_field_two
3
customer
LACSD
datetime
2020-05-21T02:27:58-07:00
documentation
PROPIPE
is_lateral_inspection
false