Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 22, 2020, 06:32 AM
  • 18 0085_18 0084 _05212020_234439.mp4

Date
05/21/2020
W/O
828920
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13904
Time
11:32 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7709
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_828920_TV18177_MAY2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0085
Downstream MH
18 0084
Dir. of Survey
Downstream
Length Surveyed
281.6 ft.
Total Length
281.6 ft.
Structural Index
3
Structural Quick
3P00
Structural Rating
258
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
258
Pipe schematic from manhole 18 0085 to 18 0084
MH: 18 0085MH: 18 0084downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 00850 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start59.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES97.5 ft. CM - Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES108 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"179.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"281.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish281.6 ft. AMH - Downstream Manhole, Survey Ends - 18 0084281.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (4)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    59.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

    97.5 ft. - Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
108TFC
281.6SAV
281.6AMH18 0084
2CM
97.5CM
2.1SAV
179.4TFC
0MWM
281.6CM
59.8CM
0AMH18 0085
0MWL
0MGOROACHES @ MH

Properties (6)

additional_info
SC411366
custom_field_two
3
customer
LACSD
datetime
2020-05-21T23:32:36-07:00
documentation
PROPIPE
is_lateral_inspection
false