Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 22, 2020, 08:47 AM
  • 18 0425_18 0076 _05222020_015504.mp4

Date
05/22/2020
W/O
828920
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00698
PipeID
P13893
Time
1:47 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7709
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_828920_TV18177_MAY2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0425
Downstream MH
18 0076
Dir. of Survey
Downstream
Length Surveyed
223.1 ft.
Total Length
223.1 ft.
Structural Index
3
Structural Quick
3H2H
Structural Rating
220
O&M Index
2
O&M Quick
312L
O&M Rating
137
Overall Index
2
Overall Quick
Overall Rating
357
Pipe schematic from manhole 18 0425 to 18 0076
MH: 18 0425MH: 18 0076downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 04250 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. MGO - General Observation - 60% MAG COAT2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start5.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start62.2 ft. ID - Infiltration Dripper, from 11 to 01 o'clock, within 8 inches of joint: YES107.9 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start159 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"221 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish223 ft. MGO - General Observation - ROACHES @ MH223.1 ft. AMH - Downstream Manhole, Survey Ends - 18 0076223.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish223.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish223.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (4)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Dripper, from 11 to 01 o'clock, within 8 inches of joint: YES

    62.2 ft. - Infiltration Dripper, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    107.9 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
2MGO60% MAG COAT
223.1AMH18 0076
0AMH18 0425
223.1SAV
223MGOROACHES @ MH
62.2ID
221DAGS
2DAGS
5.3SSS
0MWL
107.9DAE
223.1DAE
159TF
223.1SSS
5.3SAV
0MWM

Properties (6)

additional_info
SC411366
custom_field_two
2
customer
LACSD
datetime
2020-05-22T01:47:32-07:00
documentation
PROPIPE
is_lateral_inspection
false