Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 26, 2020, 10:37 AM
  • 05 1843_05 1842_6262020_034749.mp4

Date
06/26/2020
W/O
0833487
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00494
PipeID
P07067
Time
3:37 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1459
Sewer Name
05 NORTH SLOPE CONNECTION TRUNK
City
PALO VERDES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
35
Purpose
Routine Assessment
Project
20200625MDM_NORTH_SLOPE_CONNECTION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
05 1843
Downstream MH
05 1842
Dir. of Survey
Downstream
Length Surveyed
495.9 ft.
Total Length
495.9 ft.
Structural Index
2
Structural Quick
2300
Structural Rating
6
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole 05 1843 to 05 1842
MH: 05 1843MH: 05 1842downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:45AM0 ft. MWM - Water Mark, 20 %of cross sectional area28.3 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - SLIGHT29.5 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SLIGHT117.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open138.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open194.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Capped228.6 ft. MWLS - Water Level, Sag in pipe, 10 %of cross sectional area251.2 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open301.8 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open314.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open317.2 ft. MGO - General Observation - 18" VCP407.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open495.9 ft. AMH - Downstream Manhole, Survey Ends - 4:20AM

Observation photos (2)

  • Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SLIGHT

    29.5 ft. - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SLIGHT

  • General Observation - 18" VCP

    317.2 ft. - General Observation - 18" VCP

Observations (15)

DistanceCodeObservation
29.5FCSLIGHT
495.9AMH4:20AM
0MWL
407.1TFOpen
117.8TFOpen
138.4TFOpen
228.6MWLS
0AMH3:45AM
317.2MGO18" VCP
0MWM
314.8TFOpen
194.8TFCCapped
301.8TBOpen
28.3FCSLIGHT
251.2TFOpen

Properties (6)

custom_field_three
SLIGHT CIRCUM CHIPPED ,BAD LOCATION
custom_field_two
3
customer
LACSD
datetime
2020-06-26T03:37:21-07:00
documentation
MARTIN,OLIVER 111,SHADLER,BARR
is_lateral_inspection
false