Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 25, 2020, 07:15 AM
  • 05 1849_05 1848_6252020_013441.mp4

Date
06/25/2020
W/O
0833487
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00494
PipeID
P07074
Time
12:15 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1458
Sewer Name
05 NORTH SLOPE CONNECTION TRUNK
City
PALO VERDES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
35
Purpose
Routine Assessment
Project
20200625MDM_NORTH_SLOPE_CONNECTION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
05 1849
Downstream MH
05 1848
Dir. of Survey
Downstream
Length Surveyed
401.2 ft.
Total Length
401.2 ft.
Structural Index
2
Structural Quick
2200
Structural Rating
4
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 05 1849 to 05 1848
MH: 05 1849MH: 05 1848downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:35AM0 ft. MGO - General Observation - MH CONN 9:00 OPEN15.6 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT84.3 ft. FC - Fracture Circumferential, from 07 to 08 o'clock, within 8 inches of joint: YES - H110 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open162.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open172.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open199.5 ft. MWM - Water Mark, 30 %of cross sectional area212 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open262.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open299.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open324.1 ft. MGO - General Observation - 18" VCP360 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open401.2 ft. AMH - Downstream Manhole, Survey Ends - 2:05AM

Observation photos (2)

  • Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT

    15.6 ft. - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT

  • General Observation - 18" VCP

    324.1 ft. - General Observation - 18" VCP

Observations (16)

DistanceCodeObservation
0MWM
199.5MWM
0MWL
110TFOpen
401.2AMH2:05AM
172.6TFOpen
262.9TFOpen
0AMH1:35AM
15.6FCSLIGHT
324.1MGO18" VCP
212TFOpen
84.3FCH
0MGOMH CONN 9:00 OPEN
299.6TFOpen
162.1TFOpen
360TFOpen

Properties (6)

custom_field_three
FEW SLIGHT FRACTURES
custom_field_two
4
customer
LACSD
datetime
2020-06-25T00:15:09-07:00
documentation
MARTIN,SHADLER,BARR
is_lateral_inspection
false