Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 8, 2020, 09:19 PM
  • H 0698_H 0697_06082020_085026.mp4

Date
06/08/2020
W/O
828933
Weather
Dry
Operator/Surveyor
EN. RUIZ
Sewer ID
Z00941
PipeID
P11105
Time
2:19 PM
Certificate
U-116-07001919
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7761
Sewer Name
H JOINT OUTFALL H - UNIT 9B
City
WHITTIER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_828933_TV18175_MAY2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
25 in.
Width
25 in.
Upstream MH
H 0698
Downstream MH
H 0697
Dir. of Survey
Downstream
Length Surveyed
732.2 ft.
Total Length
732.2 ft.
Structural Index
3
Structural Quick
3\21
Structural Rating
437
O&M Index
2
O&M Quick
2\00
O&M Rating
290
Overall Index
3
Overall Quick
Overall Rating
727
Pipe schematic from manhole H 0698 to H 0697
MH: H 0698MH: H 0697downstream0 ft. AMH - Upstream Manhole, Survey Begins - H 06980 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area1.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES1.7 ft. SAP - Surface Aggregate Projecting, from 04 to 08 o'clock, within 8 inches of joint: YES, Start2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start729 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish729 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish732.2 ft. AMH - Downstream Manhole, Survey Ends - H 0697

Observation photos (1)

  • Surface Aggregate Projecting, from 04 to 08 o'clock, within 8 inches of joint: YES, Start

    1.7 ft. - Surface Aggregate Projecting, from 04 to 08 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
729SAP
1.7SSS
729DAGS
0AMHH 0698
0MWM
732.2AMHH 0697
0MWL
2.1DAGS
1.7SAP

Properties (6)

additional_info
SC411469
custom_field_two
3
customer
LACSD
datetime
2020-06-08T14:19:36-07:00
documentation
PRO PIPE
is_lateral_inspection
false