Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 8, 2020, 08:20 PM
  • H 0688_H 0687_06082020_132753.mp4

Date
06/08/2020
W/O
828933
Weather
Dry
Operator/Surveyor
EN. RUIZ
Sewer ID
Z00941
PipeID
P11095
Time
1:20 PM
Certificate
U-116-07001919
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7761
Sewer Name
H JOINT OUTFALL H - UNIT 9B
City
WHITTIER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_828933_TV18175_MAY2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
25 in.
Width
25 in.
Upstream MH
H 0688
Downstream MH
H 0687
Dir. of Survey
Downstream
Length Surveyed
166.8 ft.
Total Length
166.8 ft.
Structural Index
3
Structural Quick
3F2E
Structural Rating
155
O&M Index
2
O&M Quick
2F00
O&M Rating
66
Overall Index
2
Overall Quick
Overall Rating
221
Pipe schematic from manhole H 0688 to H 0687
MH: H 0688MH: H 0687downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 06882.1 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: NO, Start2.1 ft. MGO - General Observation - MAG COAT2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start22.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Start165.1 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish165.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish165.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish166.8 ft. AMH - Downstream Manhole, Survey Ends - H 0687

Observation photos (3)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

    2.1 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: NO, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

    22.9 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

Observations (11)

DistanceCodeObservation
166.8AMHH 0687
165.1SAP
165.1DAGS
0MWM
2.1SAP
0MWL
2.1MGOMAG COAT
22.9SSS
2.1DAGS
0AMHH 0688
165.1SSS

Properties (6)

additional_info
SC411469
custom_field_two
3
customer
LACSD
datetime
2020-06-08T13:20:50-07:00
documentation
PRO PIPE
is_lateral_inspection
false