Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 11, 2020, 05:47 PM
  • H 0686_H 0685_06112020_111430.mp4

Date
06/11/2020
W/O
828933
Weather
Dry
Operator/Surveyor
EN. RUIZ
Sewer ID
Z00941
PipeID
P11093
Time
10:47 AM
Certificate
U-116-07001919
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7763
Sewer Name
H JOINT OUTFALL H - UNIT 9B
City
WHITTIER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_828933_TV18175_MAY2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
25 in.
Width
25 in.
Upstream MH
H 0686
Downstream MH
H 0685
Dir. of Survey
Downstream
Length Surveyed
789 ft.
Total Length
789 ft.
Structural Index
3
Structural Quick
3^2^
Structural Rating
779
O&M Index
2
O&M Quick
2^00
O&M Rating
314
Overall Index
2
Overall Quick
Overall Rating
1093
Pipe schematic from manhole H 0686 to H 0685
MH: H 0686MH: H 0685downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 06862.1 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start17.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Start786.5 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish786.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish789 ft. AMH - Downstream Manhole, Survey Ends - H 0685789 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish

Observation photos (2)

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

    2.1 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: NO, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start

Observations (10)

DistanceCodeObservation
2.1SAV
786.5SAV
0MWL
789AMHH 0685
2.1DAGS
786.5SSS
0MWM
789DAGS
0AMHH 0686
17.1SSS

Properties (6)

additional_info
SC411473
custom_field_two
3
customer
LACSD
datetime
2020-06-11T10:47:49-07:00
documentation
PRO PIPE
is_lateral_inspection
false