Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 19, 2020, 07:04 AM
  • 15 1165_15 1164_6192020_000748.mp4

Date
06/19/2020
W/O
0828905
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00635
PipeID
P25911
Time
12:04 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1450
Sewer Name
15 TYLER AVENUE RELIEF TRUNK
City
EL MONTE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
17
Purpose
Maintenance Related
Project
20200618MDM_TYLER_AVENUE_RELIEF_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
15 1165
Downstream MH
15 1164
Dir. of Survey
Downstream
Length Surveyed
282.8 ft.
Total Length
282.8 ft.
Structural Index
2
Structural Quick
2300
Structural Rating
6
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole 15 1165 to 15 1164
MH: 15 1165MH: 15 1164downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:20AM13.5 ft. MGP - General Photograph13.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT POSSIBLE FLAKING36.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open41.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - FLAKING ROUGH SURFACE53.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open107.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active175.2 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open201 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active218.7 ft. SSS - Surface Spalling, at 02 o'clock, within 8 inches of joint: YES - POSSIBLE SPALLING218.7 ft. MGP - General Photograph - POSSIBLE SPALLING282.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SLIGHT SPALLING FLAKING282.8 ft. AMH - Downstream Manhole, Survey Ends - 1:20AM

Observation photos (5)

  • General Photograph

    13.5 ft. - General Photograph

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start -  SLIGHT POSSIBLE FLAKING

    13.5 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT POSSIBLE FLAKING

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - FLAKING ROUGH SURFACE

    41.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - FLAKING ROUGH SURFACE

  • Surface Spalling, at 02 o'clock, within 8 inches of joint: YES - POSSIBLE SPALLING

    218.7 ft. - Surface Spalling, at 02 o'clock, within 8 inches of joint: YES - POSSIBLE SPALLING

  • General Photograph - POSSIBLE SPALLING

    218.7 ft. - General Photograph - POSSIBLE SPALLING

Observations (15)

DistanceCodeObservation
13.5MGP
13.5SSSSLIGHT POSSIBLE FLAKING
41.1SSSFLAKING ROUGH SURFACE
36.1TFOpen
175.2TFOpen
53.9TFOpen
107.1TFActive
0MWM
201TFActive
0MWL
218.7SSSPOSSIBLE SPALLING
282.5SSSSLIGHT SPALLING FLAKING
218.7MGPPOSSIBLE SPALLING
282.8AMH1:20AM
0AMH12:20AM

Properties (5)

additional_info
VCP CORRISON MONITORING
customer
LACSD
datetime
2020-06-19T00:04:43-07:00
documentation
MARTIN,OLIVER 111,SHADLER
is_lateral_inspection
false