Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 18, 2020, 08:07 AM
  • 15 0849_15 0848_6182020_012528.mp4

Date
06/18/2020
W/O
0828891
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00594
PipeID
P12627
Time
1:07 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Heavy Cleaning
Media Label
H1449R
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 3&2A
City
ARACADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
01
Purpose
Maintenance Related
Project
20200617MDM_ARACADIA_SIERRA_MADRE_TRUNK_SECTS_3_2A
Material
NRCP
Shape
Circular
Height
9.399999618530273 in.
Upstream MH
15 0849
Downstream MH
15 0848
Dir. of Survey
Downstream
Length Surveyed
206.6 ft.
Total Length
206.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
4133
O&M Rating
13
Overall Index
3
Overall Quick
Overall Rating
13
Pipe schematic from manhole 15 0849 to 15 0848
MH: 15 0849MH: 15 0848downstream0 ft. MGO - General Observation - MH CONN 9:00 STUB0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:20AM72.8 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6" - Open96 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6" - Open151.9 ft. LFZ - Lining Failure Other, from 12 to 04 o'clock, within 8 inches of joint: NO - SEPERATED LINING MATERIAL151.9 ft. OBM - Obstacles Pipe Material, 25 %of cross sectional area, from 12 to 04 o'clock - SEPERATED LINING MATERIAL152.5 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6" - Open162.1 ft. TBD - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: NO, 6" - Open-100% ROOTS197.9 ft. RMC - Roots Medium Connection, from 09 to 03 o'clock, 5 %, within 8 inches of joint: NO197.9 ft. TBD - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: NO, 6" - Active-80% ROOTS204.8 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Open206.6 ft. AOC - Drop Connection, Survey Ends - 1:50AM

Observation photos (2)

  • Lining Failure Other, from 12 to 04 o'clock, within 8 inches of joint: NO - SEPERATED LINING MATERIAL

    151.9 ft. - Lining Failure Other, from 12 to 04 o'clock, within 8 inches of joint: NO - SEPERATED LINING MATERIAL

  • Obstacles Pipe Material, 25 %of cross sectional area, from 12 to 04 o'clock - SEPERATED LINING MATERIAL

    151.9 ft. - Obstacles Pipe Material, 25 %of cross sectional area, from 12 to 04 o'clock - SEPERATED LINING MATERIAL

Observations (14)

DistanceCodeObservation
151.9LFZSEPERATED LINING MATERIAL
206.6AOC1:50AM
162.1TBDOpen-100% ROOTS
197.9RMC
0MGOMH CONN 9:00 STUB
0MWM
96TBOpen
72.8TBOpen
197.9TBDActive-80% ROOTS
0MWL
152.5TBOpen
204.8TBOpen
151.9OBMSEPERATED LINING MATERIAL
0AMH1:20AM

Properties (6)

additional_info
POST ROOT EVALUATION ONLY
customer
LACSD
datetime
2020-06-18T01:07:14-07:00
documentation
MARTIN,SHADLER
is_lateral_inspection
false
lining
CIPP