Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 28, 2020, 07:46 AM
  • 02 0388_02 0387A _05282020_010300.mp4

Date
05/28/2020
W/O
828846
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00250
PipeID
P02707
Time
12:46 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7674
Sewer Name
02 DOWNEY AVENUE EXTENSION TRUNK
City
PARAMOUNT
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_828846_TV02126_MAY2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 0388
Downstream MH
02 0387A
Dir. of Survey
Downstream
Length Surveyed
315.1 ft.
Total Length
315.1 ft.
Structural Index
3
Structural Quick
413K
Structural Rating
190
O&M Index
2
O&M Quick
412K
O&M Rating
128
Overall Index
3
Overall Quick
Overall Rating
318
Pipe schematic from manhole 02 0388 to 02 0387A
MH: 02 0388MH: 02 0387Adownstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 03880 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start4 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start29.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"61.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"89 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"92.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"184.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"188.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"226 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"229.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"265.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"268.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"312.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish312.7 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish315.1 ft. AMH - Downstream Manhole, Survey Ends - 02 0387A315.1 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK315.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    4 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    92.7 ft. - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • General Observation - COCKROACHES IN MANHOLE

    315.1 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (21)

DistanceCodeObservation
61.4TF
0MWM
315.1AMH02 0387A
268.7TFA
0AMH02 0388
188.2TF
29.9TFA
2DAGS
4FM
184.6TFC
5CM
226TFA
315.1MGOCONNECTION AT MH 9 O'CLOCK
0MWL
312.7DAGS
315.1MGOCOCKROACHES IN MANHOLE
312.7CM
92.7TFA
265.2TFC
229.1TFC
89TFA

Properties (6)

additional_info
SC411266
custom_field_two
2
customer
LACSD
datetime
2020-05-28T00:46:22-07:00
documentation
PRO PIPE
is_lateral_inspection
false