Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 28, 2020, 06:28 AM
  • 02 0366A_02 0366 _05272020_234534.mp4

Date
05/27/2020
W/O
828846
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00250
PipeID
P02681
Time
11:28 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7674
Sewer Name
02 DOWNEY AVENUE EXTENSION TRUNK
City
PARAMOUNT
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
02
Purpose
Routine Assessment
Project
RFIR_WO_828846_TV02126_MAY2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0366A
Downstream MH
02 0366
Dir. of Survey
Downstream
Length Surveyed
300.7 ft.
Total Length
300.7 ft.
Structural Index
3
Structural Quick
513K
Structural Rating
179
O&M Index
2
O&M Quick
2K00
O&M Rating
120
Overall Index
3
Overall Quick
Overall Rating
299
Pipe schematic from manhole 02 0366A to 02 0366
MH: 02 0366AMH: 02 0366downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 0366A0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 5 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start11.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start16.2 ft. HVV - Hole Void Visible, from 12 to 03 o'clock, within 8 inches of joint: YES16.2 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"23.1 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"65.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"77 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"112.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"127.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"163.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"173.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"210 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES212.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6" - INTRUDING, ,0.5"227.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"263.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"274.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"298.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE298.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish298.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish300.7 ft. AMH - Downstream Manhole, Survey Ends - 02 0366

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    11.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Hole Void Visible, from 12 to 03 o'clock, within 8 inches of joint: YES

    16.2 ft. - Hole Void Visible, from 12 to 03 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    298.5 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (25)

DistanceCodeObservation
0AMH02 0366A
300.7AMH02 0366
173.7TF
227.9TFC
112.5TFA
0MGOCOCKROACHES IN MANHOLE
127.6TF
16.2HVV
212.4TFAINTRUDING, ,0.5"
263.1TF
0MWL
0MGOCONNECTION AT MH 9 O'CLOCK
11.6CM
0MWM
210FL
77TFC
65.6TFC
23.1TBC
298.5MGOCOCKROACHES IN MANHOLE
298.5CM
163.2TFA
298.5DAGS
16.2TBA
2DAGS
274.4TFC

Properties (6)

additional_info
SC411266
custom_field_two
1
customer
LACSD
datetime
2020-05-27T23:28:38-07:00
documentation
PRO PIPE
is_lateral_inspection
false