Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 8, 2020, 07:32 AM
  • 21 0487_21 0486 _05082020_004733.mp4

Date
05/08/2020
W/O
828762
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00779
PipeID
P15696
Time
12:32 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7654
Sewer Name
21 PHILLIPS BOULEVARD TRUNK
City
POMONA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
15
Purpose
Routine Assessment
Project
WO_828762_TV21017_MAY2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
21 0487
Downstream MH
21 0486
Dir. of Survey
Downstream
Length Surveyed
395 ft.
Total Length
395 ft.
Structural Index
3
Structural Quick
3O2O
Structural Rating
390
O&M Index
2
O&M Quick
2^00
O&M Rating
312
Overall Index
2
Overall Quick
Overall Rating
702
Pipe schematic from manhole 21 0487 to 21 0486
MH: 21 0487MH: 21 0486downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 21 04872 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start4.9 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start - DEBRIS4.9 ft. MGO - General Observation - MAG COATING THROUGHOUT393 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish393.7 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish393.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish393.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish395 ft. MGO - General Observation - COCKROACHES IN MANHOLE395 ft. AMH - Downstream Manhole, Survey Ends - 21 0486

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Settled Other,  5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start - DEBRIS

    4.9 ft. - Deposits Settled Other, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start - DEBRIS

  • General Observation - MAG COATING THROUGHOUT

    4.9 ft. - General Observation - MAG COATING THROUGHOUT

  • General Observation - COCKROACHES IN MANHOLE

    395 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (15)

DistanceCodeObservation
0MGOCOCKROACHES IN MANHOLE
0MWL
4.9DSZDEBRIS
393.7DSZ
395MGOCOCKROACHES IN MANHOLE
393SSS
0MWM
395AMH21 0486
393.7SAV
2SAV
2DAGS
0AMH21 0487
393.7DAGS
2SSS
4.9MGOMAG COATING THROUGHOUT

Properties (6)

additional_info
SC411245
custom_field_two
3
customer
LACSD
datetime
2020-05-08T00:32:00-07:00
documentation
PRO PIPE
is_lateral_inspection
false