Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 7, 2020, 08:41 AM
  • 21 0502_21 1165 _05072020_014721.mp4

Date
05/07/2020
W/O
828762
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00779
PipeID
P15712
Time
1:41 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7653
Sewer Name
21 PHILLIPS BOULEVARD TRUNK
City
POMONA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
20
Purpose
Routine Assessment
Project
WO_828762_TV21017_MAY2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
21 0502
Downstream MH
21 1165
Dir. of Survey
Downstream
Length Surveyed
152.9 ft.
Total Length
153 ft.
Structural Index
3
Structural Quick
3E00
Structural Rating
90
O&M Index
2
O&M Quick
2E00
O&M Rating
60
Overall Index
3
Overall Quick
Overall Rating
150
Pipe schematic from manhole 21 0502 to 21 1165
MH: 21 0502MH: 21 1165downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 21 05020 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area3.1 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start3.1 ft. MGO - General Observation - MAG COATING THROUGHOUT151.6 ft. MGO - General Observation - COCKROACHES IN MANHOLE151.6 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish151.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish153 ft. AMH - Downstream Manhole, Survey Ends - 21 1165153 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    0 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COATING THROUGHOUT

    3.1 ft. - General Observation - MAG COATING THROUGHOUT

  • General Observation - COCKROACHES IN MANHOLE

    151.6 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (12)

DistanceCodeObservation
0MGOCOCKROACHES IN MANHOLE
151.6MGOCOCKROACHES IN MANHOLE
0AMH21 0502
153AMH21 1165
151.6SAP
153MGOCONNECTION AT MH 9 O'CLOCK
0DAGS
0MWL
151.6DAGS
0MWM
3.1SAP
3.1MGOMAG COATING THROUGHOUT

Properties (6)

additional_info
SC411244
custom_field_two
3
customer
LACSD
datetime
2020-05-07T01:41:04-07:00
documentation
PRO PIPE
is_lateral_inspection
false