Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 13, 2020, 07:31 AM
  • H 0788_H 0787 _05132020_003456.mp4

Date
05/13/2020
W/O
824117
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00942
PipeID
P11196
Time
12:31 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7600
Sewer Name
H JOINT OUTFALL H - UNIT 9C
City
SAN DIMAS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_824117_TV22079_APR2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
20 in.
Width
20 in.
Upstream MH
H 0788
Downstream MH
H 0787
Dir. of Survey
Downstream
Length Surveyed
2.1 ft.
Total Length
2.1 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
4
O&M Quick
5221
O&M Rating
12
Overall Index
4
Overall Quick
Overall Rating
14
Pipe schematic from manhole H 0788 to H 0787
MH: H 0788MH: H 0787downstream0 ft. MWM - Water Mark, 85 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 07880 ft. MWL - Water Level, 15 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES2.1 ft. DSZ - Deposits Settled Other, 35 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES - SLUDGE2.1 ft. MSA - Survey Abandoned - CAM BLKD BY SLUDGE

Observation photos (1)

  • Deposits Settled Other,  35 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES - SLUDGE

    2.1 ft. - Deposits Settled Other, 35 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES - SLUDGE

Observations (7)

DistanceCodeObservation
0MWM
2SSS
2DAGS
2.1DSZSLUDGE
0AMHH 0788
2.1MSACAM BLKD BY SLUDGE
0MWL

Properties (6)

additional_info
SC411357
custom_field_two
5
customer
LACSD
datetime
2020-05-13T00:31:58-07:00
documentation
PROPIPE
is_lateral_inspection
false