Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 14, 2020, 05:28 AM
  • H 0785A_H 0785 _05132020_230832.mp4

Date
05/13/2020
W/O
824117
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00942
PipeID
P11194
Time
10:28 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7701
Sewer Name
H JOINT OUTFALL H - UNIT 9C
City
COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_824117_TV22079_APR2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
20 in.
Width
20 in.
Upstream MH
H 0785A
Downstream MH
H 0785
Dir. of Survey
Downstream
Length Surveyed
1105.6 ft.
Total Length
1105.6 ft.
Structural Index
3
Structural Quick
3k2k
Structural Rating
1103
O&M Index
3
O&M Quick
3k2k
O&M Rating
1103
Overall Index
3
Overall Quick
Overall Rating
2206
Pipe schematic from manhole H 0785A to H 0785
MH: H 0785AMH: H 0785downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 0785A2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.3 ft. MGO - General Observation - MAG COAT2.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.3 ft. DSZ - Deposits Settled Other, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start - SLUDGE438.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN493.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN653.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN1103 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish1103 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1105 ft. MGO - General Observation - POSSIBLE ABANDONED MH1105.6 ft. AMH - Downstream Manhole, Survey Ends - H 07851105.6 ft. DSZ - Deposits Settled Other, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish - SLUDGE1105.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Settled Other,  20 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start - SLUDGE

    2.3 ft. - Deposits Settled Other, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start - SLUDGE

Observations (17)

DistanceCodeObservation
2DAGS
1105.6AMHH 0785
653.6TFOPEN
2.3MGOMAG COAT
0MWL
1105.6DSZSLUDGE
1103DAGS
2.3SAV
2SSS
2.3DSZSLUDGE
1105MGOPOSSIBLE ABANDONED MH
493.1TFOPEN
1105.6SAV
0MWM
438.7TFOPEN
1103SSS
0AMHH 0785A

Properties (6)

additional_info
SC411358
custom_field_two
3
customer
LACSD
datetime
2020-05-13T22:28:18-07:00
documentation
PROPIPE
is_lateral_inspection
false