Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 9, 2020, 08:47 AM
  • B 0184_B 0183A_692020_033739.mp4

Date
06/09/2020
W/O
0828888
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00075
PipeID
P08668
Time
1:47 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1442
Sewer Name
B JOINT OUTFALL B - UNIT 1D
City
MONTEBELLO
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
19
Purpose
Capital Improvement Program Assesment
Project
20200609MDM_JOINT_OUTFALL_B_UNIT_1D
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Upstream MH
B 0184
Downstream MH
B 0183A
Dir. of Survey
Downstream
Length Surveyed
627.8 ft.
Total Length
627.8 ft.
Structural Index
5
Structural Quick
5542
Structural Rating
33
O&M Index
3
O&M Quick
4122
O&M Rating
8
Overall Index
4
Overall Quick
Overall Rating
41
Pipe schematic from manhole B 0184 to B 0183A
MH: B 0184MH: B 0183Adownstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:40AM0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR CORRODED & MISSING53.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR105.8 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR148.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR171.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 09 to 10 o'clock, , within 8 inches of joint: YES, Start366.2 ft. RFB - Roots Fine Barrell, from 02 to 04 o'clock, within 8 inches of joint: NO - 4%457.7 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG539.9 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR CORRODED & MISSING627.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 09 to 10 o'clock, , within 8 inches of joint: YES, Finish627.3 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG627.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR CORRODED & MISSING627.8 ft. AMH - Downstream Manhole, Survey Ends - 4:40AM

Observation photos (7)

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR CORRODED & MISSING

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR CORRODED & MISSING

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    105.8 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    148.7 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Deposits Attached Grease, 5 %of cross sectional area, from 09 to 10 o'clock,  , within 8 inches of joint: YES, Start

    171.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 09 to 10 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    457.7 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR CORRODED & MISSING

    539.9 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR CORRODED & MISSING

Observations (16)

DistanceCodeObservation
53.3SRCCIRCUM REBAR
627.3DAGS
366.2RFB4%
539.9SRCCIRCUM REBAR CORRODED & MISSING
627.3SAMSEVERE AGG
457.7SAMSEVERE AGG
171.3DAGS
0MWM
0AMH3:40AM
2SAMSEVERE AGG
2SRCCIRCUM REBAR CORRODED & MISSING
105.8SRCCIRCUM REBAR
0MWL
627.3SRCCIRCUM REBAR CORRODED & MISSING
148.7SRCCIRCUM REBAR
627.8AMH4:40AM

Properties (6)

custom_field_three
CIRCUM REBAR CORRODED & MISSING
custom_field_two
1
customer
LACSD
datetime
2020-06-09T01:47:12-07:00
documentation
MARTIN,OLIVER 111,SHADLER.SKINNER
is_lateral_inspection
false