- Date
- 06/09/2020
- W/O
- 0828888
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00075
- PipeID
- P08669
- Time
- 1:47 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H1442
- Sewer Name
- B JOINT OUTFALL B - UNIT 1D
- City
- MONTEBELLO
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 02
- Page No.
- 19
- Purpose
- Capital Improvement Program Assesment
- Project
- 20200609MDM_JOINT_OUTFALL_B_UNIT_1D
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 57 in.
- Upstream MH
- B 0184A
- Downstream MH
- B 0184
- Dir. of Survey
- Downstream
- Length Surveyed
- 549.8 ft.
- Total Length
- 549.8 ft.
- Structural Index
- 5
- Structural Quick
- 5341
- Structural Rating
- 19
- O&M Index
- 3
- O&M Quick
- 4121
- O&M Rating
- 6
- Overall Index
- 4
- Overall Quick
- —
- Overall Rating
- 25
Pipe schematic from manhole B 0184A to B 0184 Observation photos (5)

2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG &CIRCUM REBAR

2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

246.2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR CORRODED & MISSING

268.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 04 o'clock, , within 8 inches of joint: YES, Start

415 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR CORRODED & MISSING