Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 5, 2020, 04:23 AM
  • H 0585_H 0584 _05042020_213350.mp4

Date
05/04/2020
W/O
828833
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00188
PipeID
P11008
Time
9:23 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7651
Sewer Name
H JOINT OUTFALL H - UNIT 8E
City
WEST COVINA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
19
Purpose
Routine Assessment
Project
WO_828833_TV15173_MAY2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
H 0585
Downstream MH
H 0584
Dir. of Survey
Downstream
Length Surveyed
327.8 ft.
Total Length
327.8 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
183
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
187
Pipe schematic from manhole H 0585 to H 0584
MH: H 0585MH: H 0584downstream0 ft. AMH - Upstream Manhole, Survey Begins - H 05850 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. MGO - General Observation - MAG COATING THROUGHOUT4.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"12.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"21.8 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start54.8 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"124.4 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"167 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"231.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"239.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"325.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish327.8 ft. AMH - Downstream Manhole, Survey Ends - H 0584327.8 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (3)

  • General Observation - MAG COATING THROUGHOUT

    2 ft. - General Observation - MAG COATING THROUGHOUT

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    21.8 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    327.8 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (15)

DistanceCodeObservation
21.8SAP
54.8TBA
124.4TBA
325.2SAP
12.7TFC
0AMHH 0585
4.4TFC
2MGOMAG COATING THROUGHOUT
0MWL
231.7TFC
327.8AMHH 0584
167TB
327.8MGOCOCKROACHES IN MANHOLE
0MWM
239.9TF

Properties (6)

additional_info
SC411242
custom_field_two
2
customer
LACSD
datetime
2020-05-04T21:23:13-07:00
documentation
PRO PIPE
is_lateral_inspection
false