Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 5, 2020, 05:19 AM
  • H 0583_H 0582 _05042020_223534.mp4

Date
05/04/2020
W/O
828833
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00188
PipeID
P11006
Time
10:19 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7651
Sewer Name
H JOINT OUTFALL H - UNIT 8E
City
WEST COVINA
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
19
Purpose
Routine Assessment
Project
WO_828833_TV15173_MAY2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
H 0583
Downstream MH
H 0582
Dir. of Survey
Downstream
Length Surveyed
534 ft.
Total Length
534 ft.
Structural Index
3
Structural Quick
3T00
Structural Rating
315
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
315
Pipe schematic from manhole H 0583 to H 0582
MH: H 0583MH: H 0582downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 05832 ft. MGO - General Observation - MAG COATING THROUGHOUT8.7 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start85.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"311.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"532.8 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish534 ft. AMH - Downstream Manhole, Survey Ends - H 0582

Observation photos (3)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • General Observation - MAG COATING THROUGHOUT

    2 ft. - General Observation - MAG COATING THROUGHOUT

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    8.7 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
0MWM
8.7SAP
0MGOCOCKROACHES IN MANHOLE
2MGOMAG COATING THROUGHOUT
534AMHH 0582
311.7TFC
0MWL
0AMHH 0583
85.3TFC
532.8SAP

Properties (6)

additional_info
SC411242
custom_field_two
2
customer
LACSD
datetime
2020-05-04T22:19:48-07:00
documentation
PRO PIPE
is_lateral_inspection
false