Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 5, 2020, 08:48 AM
  • H 0573_H 0572 _05052020_020128.mp4

Date
05/05/2020
W/O
828833
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00188
PipeID
P10997
Time
1:48 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7651
Sewer Name
H JOINT OUTFALL H - UNIT 8E
City
BALDWIN PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
19
Purpose
Routine Assessment
Project
WO_828833_TV15173_MAY2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
H 0573
Downstream MH
H 0572
Dir. of Survey
Downstream
Length Surveyed
301.2 ft.
Total Length
301.2 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
177
O&M Index
2
O&M Quick
412K
O&M Rating
124
Overall Index
3
Overall Quick
Overall Rating
301
Pipe schematic from manhole H 0573 to H 0572
MH: H 0573MH: H 0572downstream0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - H 05730 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start3.5 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start23.3 ft. MGO - General Observation - MAG COATING THROUGHOUT69.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"85.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"125.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"141.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"158 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"206.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6" - FINE ROOTS IN CONNECTION222.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"270.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"299 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish301.2 ft. AMH - Downstream Manhole, Survey Ends - H 0572301.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish301.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE301.2 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3.5 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COATING THROUGHOUT

    23.3 ft. - General Observation - MAG COATING THROUGHOUT

  • General Observation - COCKROACHES IN MANHOLE

    301.2 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (21)

DistanceCodeObservation
125.7TFC
301.2AMHH 0572
0MWL
0MWM
222.3TFC
0MGOCONNECTION AT MH 3 O'CLOCK
85.8TFA
2DAGS
301.2DAGS
3.5SAP
301.2MGOCOCKROACHES IN MANHOLE
158TFC
69.2TFA
270.9TFA
23.3MGOMAG COATING THROUGHOUT
0AMHH 0573
206.3TFAFINE ROOTS IN CONNECTION
301.2MGOCONNECTION AT MH 3 O'CLOCK
141.8TFA
0MGOCOCKROACHES IN MANHOLE
299SAP

Properties (6)

additional_info
SC411242
custom_field_two
3
customer
LACSD
datetime
2020-05-05T01:48:18-07:00
documentation
PRO PIPE
is_lateral_inspection
false