Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 27, 2020, 01:59 PM
  • H 0395_H 0394_04272020_071154.mp4

Date
04/27/2020
W/O
823965
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00177
PipeID
P10824
Time
6:59 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7583
Sewer Name
H JOINT OUTFALL H - UNIT 5A
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_823965_TV18073_APR2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
51 in.
Width
51 in.
Upstream MH
H 0395
Downstream MH
H 0394
Dir. of Survey
Downstream
Length Surveyed
483.6 ft.
Total Length
483.6 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole H 0395 to H 0394
MH: H 0395MH: H 0394downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 03942.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - MAG COAT482.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish483.6 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK483.6 ft. AMH - Downstream Manhole, Survey Ends - H 0394

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0MWL
0MWM
0AMHH 0394
483.6MGOCONNECTION AT MH 3 O'CLOCK
483.6AMHH 0394
482.3SAV
2.1SAV
2.1MGOMAG COAT

Properties (6)

additional_info
SC411142
custom_field_two
3
customer
LACSD
datetime
2020-04-27T06:59:31-07:00
documentation
PROPIPE
is_lateral_inspection
false