Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 29, 2020, 05:01 PM
  • H 0391_H 0390 _04292020_102105.mp4

Date
04/29/2020
W/O
823965
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00177
PipeID
P10820
Time
10:01 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7585
Sewer Name
H JOINT OUTFALL H - UNIT 5A
City
PICO RIVERA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
03
Purpose
Routine Assessment
Project
RFIR_WO_823965_TV18073_APR2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Width
54 in.
Upstream MH
H 0391
Downstream MH
H 0390
Dir. of Survey
Downstream
Length Surveyed
783.4 ft.
Total Length
783.4 ft.
Structural Index
3
Structural Quick
3^00
Structural Rating
468
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
468
Pipe schematic from manhole H 0391 to H 0390
MH: H 0391MH: H 0390downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 03910 ft. MWL - Water Level, 20 %of cross sectional area3.1 ft. MGO - General Observation - MAG COATING ATTATCHED3.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start783.4 ft. AMH - Downstream Manhole, Survey Ends - H 0390783.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
0MWM
3.1MGOMAG COATING ATTATCHED
0AMHH 0391
0MWL
783.4AMHH 0390
3.1SAV
783.4SAV

Properties (6)

additional_info
SC411144
custom_field_two
3
customer
LACSD
datetime
2020-04-29T10:01:25-07:00
documentation
PROPIPE
is_lateral_inspection
false