Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 21, 2020, 09:45 AM
  • H 0388_H 0387 _04212020_025450.mp4

Date
04/21/2020
W/O
823965
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00177
PipeID
P10817
Time
2:45 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7573
Sewer Name
H JOINT OUTFALL H - UNIT 5A
City
CITY OF INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
03
Purpose
Routine Assessment
Project
RFIR_WO_823965_TV18073_APR2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
H 0388
Downstream MH
H 0387
Dir. of Survey
Downstream
Length Surveyed
352.3 ft.
Total Length
352.3 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole H 0388 to H 0387
MH: H 0388MH: H 0387downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 03882.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - MAG COAT351.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish351.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK352.3 ft. AMH - Downstream Manhole, Survey Ends - H 0387

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
351.9MGOCONNECTION AT MH 9 O'CLOCK
0MWL
0MWM
2.1SAV
2.1MGOMAG COAT
0AMHH 0388
352.3AMHH 0387
351.4SAV

Properties (6)

additional_info
SC411132
custom_field_two
3
customer
LACSD
datetime
2020-04-21T02:45:33-07:00
documentation
PROPIPE
is_lateral_inspection
false