Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 22, 2020, 04:41 AM
  • H 0383_H 0382_04212020_214854.mp4

Date
04/21/2020
W/O
823965
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00177
PipeID
P10812
Time
9:41 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7574
Sewer Name
H JOINT OUTFALL H - UNIT 5A
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
03
Purpose
Routine Assessment
Project
RFIR_WO_823965_TV18073_APR2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
60 in.
Width
60 in.
Upstream MH
H 0383
Downstream MH
H 0382
Dir. of Survey
Downstream
Length Surveyed
256.9 ft.
Total Length
256.9 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole H 0383 to H 0382
MH: H 0383MH: H 0382downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 03832.1 ft. MGO - General Observation - MAG COAT2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start69.2 ft. MGO - General Observation - HEAVY STEAM139.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"256.9 ft. AMH - Downstream Manhole, Survey Ends - H 0382256.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
256.9AMHH 0382
69.2MGOHEAVY STEAM
0MWL
139.8TF
0MGOCONNECTION AT MH 3 O'CLOCK
2.1MGOMAG COAT
256.9SAV
0MWM
2.1SAV
0AMHH 0383

Properties (6)

additional_info
SC411133
custom_field_two
3
customer
LACSD
datetime
2020-04-21T21:41:29-07:00
documentation
PROPIPE
is_lateral_inspection
false