Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 9, 2020, 07:19 AM
  • 05 1095_05 1094_04092020_003458.mp4

Date
04/09/2020
W/O
818458
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00488
PipeID
P06329
Time
12:19 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7559
Sewer Name
05 MONETA EXTENSION TRUNK, SECTION 1
City
GARDENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_818458_TV05328_MAR2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
05 1095
Downstream MH
05 1094
Dir. of Survey
Downstream
Length Surveyed
324.5 ft.
Total Length
324.5 ft.
Structural Index
3
Structural Quick
3300
Structural Rating
9
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole 05 1095 to 05 1094
MH: 05 1095MH: 05 1094downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 10953.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start48.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"59.1 ft. FS - Fracture Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES149.2 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"195.3 ft. FS - Fracture Spiral, from 12 to 05 o'clock, within 8 inches of joint: YES246.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"324.5 ft. AMH - Downstream Manhole, Survey Ends - 05 1094324.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES

    59.1 ft. - Fracture Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 12 to 05 o'clock, within 8 inches of joint: YES

    195.3 ft. - Fracture Spiral, from 12 to 05 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
195.3FS
59.1FS
0MWM
324.5AMH05 1094
48.4TFC
149.2TFA
246.9TFC
0MWL
324.5CM
3.9CM
0AMH05 1095

Properties (6)

additional_info
SC41118
custom_field_two
3
customer
LACSD
datetime
2020-04-09T00:19:03-07:00
documentation
PROPIPE
is_lateral_inspection
false