Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 24, 2020, 07:49 AM
  • H 0145_H 0144_04242020_011850.mp4

Date
04/24/2020
W/O
823804
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00166
PipeID
P20585
Time
12:49 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7619
Sewer Name
H JOINT OUTFALL H - UNIT 1G
City
HUNTINGTON PARK
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
03
Purpose
Routine Assessment
Project
RFIR_WO_823804_TV23004_APR2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Width
42 in.
Upstream MH
H 0145
Downstream MH
H 0144
Dir. of Survey
Downstream
Length Surveyed
442.2 ft.
Total Length
442.2 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
216
O&M Index
2
O&M Quick
2P14
O&M Rating
176
Overall Index
2
Overall Quick
Overall Rating
392
Pipe schematic from manhole H 0145 to H 0144
MH: H 0145MH: H 0144downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 01450 ft. MWL - Water Level, 15 %of cross sectional area10.5 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start25.5 ft. MGO - General Observation - STEAM IN MH82 ft. MMC - Material Change, Reinforced concrete pipe - DB SHOWS VCP84.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start424.5 ft. LL - Alignment Left, 10 %, Start442.2 ft. LL - Alignment Left, 10 %, Finish442.2 ft. MSA - Survey Abandoned - SHARP BEND IN PIPE442.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish442.2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (2)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    10.5 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    84.4 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
442.2LL
82MMCDB SHOWS VCP
442.2MSASHARP BEND IN PIPE
442.2SAP
442.2DAE
10.5DAE
0MWM
0AMHH 0145
84.4SAP
0MWL
424.5LL
25.5MGOSTEAM IN MH

Properties (6)

additional_info
SC411169
custom_field_two
5
customer
LACSD
datetime
2020-04-24T00:49:16-07:00
documentation
PROPIPE
is_lateral_inspection
false