Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 15, 2020, 09:24 AM
  • 15 0343_15 0342A _04152020_023140.mp4

Date
04/15/2020
W/O
823765
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00598
PipeID
P20532
Time
2:24 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7523
Sewer Name
15 BALDWIN PARK TRUNK
City
BALDWIN PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
24
Purpose
Routine Assessment
Project
RFIR_WO_823765_TV15018_APR2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
15 0343
Downstream MH
15 0342A
Dir. of Survey
Downstream
Length Surveyed
173.6 ft.
Total Length
173.6 ft.
Structural Index
3
Structural Quick
3F2F
Structural Rating
170
O&M Index
2
O&M Quick
412F
O&M Rating
72
Overall Index
2
Overall Quick
Overall Rating
242
Pipe schematic from manhole 15 0343 to 15 0342A
MH: 15 0343MH: 15 0342Adownstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 03430 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start20.8 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"27.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"129.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"171.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish171.9 ft. MGO - General Observation - COCKROACHES IN MANHOLE171.9 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish171.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish173.6 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK173.6 ft. AMH - Downstream Manhole, Survey Ends - 15 0342A

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    171.9 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (16)

DistanceCodeObservation
171.9DAGS
2SSS
0MGOCONNECTION AT MH 9 O'CLOCK
27.8TFC
129.2TFC
20.8TBA
171.9MGOCOCKROACHES IN MANHOLE
0MWL
2DAGS
173.6MGOCONNECTION AT MH 9 O'CLOCK
171.9SAP
171.9SSS
0AMH15 0343
2SAP
173.6AMH15 0342A
0MWM

Properties (6)

additional_info
SC411214
custom_field_two
2
customer
LACSD
datetime
2020-04-15T02:24:26-07:00
documentation
PRO PIPE
is_lateral_inspection
false