Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 15, 2020, 05:43 AM
  • B 0228_B 0227 _04142020_234114.mp4

Date
04/14/2020
W/O
818338
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00085
PipeID
P08808
Time
10:43 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7610
Sewer Name
B JOINT OUTFALL B - UNIT 2B
City
S. EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
27
Purpose
Routine Assessment
Project
RFIR_WO_818338_TV15147_MAR2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Width
57 in.
Upstream MH
B 0228
Downstream MH
B 0227
Dir. of Survey
Downstream
Length Surveyed
1333.6 ft.
Total Length
1333.6 ft.
Structural Index
3
Structural Quick
3t2S
Structural Rating
994
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
994
Pipe schematic from manhole B 0228 to B 0227
MH: B 0228MH: B 0227downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 02280 ft. MWM - Water Mark, 40 %of cross sectional area10.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start10.5 ft. MGO - General Observation - MAG COATING ATTATCHED827.8 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start963.7 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 12"1332.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1332.6 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish1332.9 ft. MGO - General Observation - CONNECTION IN MH, 9 O' CLOCK1333.6 ft. AMH - Downstream Manhole, Survey Ends - B 0227

Observations (11)

DistanceCodeObservation
827.8SSS
1332.6SAP
1333.6AMHB 0227
0MWL
0AMHB 0228
1332.9MGOCONNECTION IN MH, 9 O' CLOCK
1332.6SSS
0MWM
10.5SAP
963.7TB
10.5MGOMAG COATING ATTATCHED

Properties (6)

additional_info
SC411160
custom_field_two
3
customer
LACSD
datetime
2020-04-14T22:43:14-07:00
documentation
PROPIPE
is_lateral_inspection
false