Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 23, 2020, 04:05 AM
  • F 0177_F 0176 _04222020_212018.mp4

Date
04/22/2020
W/O
824289
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00044
PipeID
P10310
Time
9:05 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7576
Sewer Name
F JOINT OUTFALL F - UNIT 7B
City
NORWALK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
34
Purpose
Routine Assessment
Project
RFIR_WO_824289_TV18094_APR2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
F 0177
Downstream MH
F 0176
Dir. of Survey
Downstream
Length Surveyed
326.1 ft.
Total Length
326.1 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole F 0177 to F 0176
MH: F 0177MH: F 0176downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - F 01770 ft. MWM - Water Mark, 25 %of cross sectional area2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start107.8 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start324.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish326.1 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK326.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish326.1 ft. AMH - Downstream Manhole, Survey Ends - F 0176

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    107.8 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0MWL
2.1SAP
326.1MGOCONNECTION AT MH 3 O'CLOCK
326.1SRV
107.8SRV
0AMHF 0177
326.1AMHF 0176
0MWM
324.5SAP

Properties (6)

additional_info
SC411135
custom_field_two
2
customer
LACSD
datetime
2020-04-22T21:05:44-07:00
documentation
PROPIPE
is_lateral_inspection
false