Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 16, 2020, 10:08 AM
  • 01 0017_01 0016_04162020_032116.mp4

Date
04/16/2020
W/O
823873
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00209
PipeID
P00682
Time
3:08 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7571
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
16
Purpose
Routine Assessment
Project
RFIR_WO_823873_TV01245_APR2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
01 0017
Downstream MH
01 0016
Dir. of Survey
Downstream
Length Surveyed
425 ft.
Total Length
425 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 01 0017 to 01 0016
MH: 01 0017MH: 01 0016downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 00170 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK2.1 ft. MGO - General Observation - HEAVY STEAM3.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES5.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start258 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"329.8 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"382.9 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"425 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish425 ft. AMH - Downstream Manhole, Survey Ends - 01 0016

Observation photos (5)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    3.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    258 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    329.8 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    382.9 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (13)

DistanceCodeObservation
0MWM
258TB
0MWL
0AMH01 0017
0MGOCONNECTION AT MH 3 O'CLOCK
425CM
3.4CL
2.1MGOHEAVY STEAM
425AMH01 0016
329.8TB
5.7CM
382.9TB
0MGOCONNECTION AT MH 9 O'CLOCK

Properties (6)

additional_info
SC411130
custom_field_two
3
customer
LACSD
datetime
2020-04-16T03:08:20-07:00
documentation
PROPIPE
is_lateral_inspection
false