Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 21, 2020, 10:33 AM
  • 01 0631_01 0630_5212020_034154.mp4

Date
05/21/2020
W/O
0829299
Weather
Dry
Operator/Surveyor
U-115-06022630
Sewer ID
Z00212
PipeID
P01127
Time
3:33 AM
Certificate
U-115-06022630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1425
Sewer Name
01 MOUNTAIN VIEW-BELLE VERNON TRUNK
City
HUNTINGTON PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
20200519VMR_MOUNTAIN_VIEW_BELLE_VERNON_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
01 0631
Downstream MH
01 0630
Dir. of Survey
Downstream
Length Surveyed
220.8 ft.
Total Length
220.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 01 0631 to 01 0630
MH: 01 0631MH: 01 0630downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 03:39 AM2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 04 o'clock, , within 8 inches of joint: NO, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 09 o'clock, , within 8 inches of joint: NO, Start62.4 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 4"113.8 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 4"169.9 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 4"213.3 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 4"217.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 04 o'clock, , within 8 inches of joint: NO, Finish217.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 09 o'clock, , within 8 inches of joint: NO, Finish220.8 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"220.8 ft. AMH - Downstream Manhole, Survey Ends - 03:54 AM

Observations (13)

DistanceCodeObservation
2DAGS
0MWM
213.3TF
2DAGS
0MWL
169.9TF
62.4TF
217.5DAGS
220.8TFC
0AMH03:39 AM
113.8TF
220.8AMH03:54 AM
217.5DAGS

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2020-05-21T03:33:28-07:00
documentation
REVELES, OLIVER III, CASTILLO, SKINNER
is_lateral_inspection
false