Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 19, 2020, 06:58 AM
  • 01 0655_01 0654_5182020_001038.mp4

Date
05/18/2020
W/O
0829299
Weather
Dry
Operator/Surveyor
U-115-06022630
Sewer ID
Z00212
PipeID
P01155
Time
11:58 PM
Certificate
U-115-06022630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1422
Sewer Name
01 MOUNTAIN VIEW-BELLE VERNON TRUNK
City
HUNTINGTON PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
20200519VMR_MOUNTAIN_VIEW_BELLE_VERNON_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
01 0655
Downstream MH
01 0654
Dir. of Survey
Downstream
Length Surveyed
316.1 ft.
Total Length
316.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2211
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
5
Pipe schematic from manhole 01 0655 to 01 0654
MH: 01 0655MH: 01 0654downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:01 AM0 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4"0 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 4"0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 05 o'clock, , within 8 inches of joint: YES, Start58.5 ft. SZ - Surface Other, at 01 o'clock, within 8 inches of joint: NO - PATCH82.4 ft. SZ - Surface Other, at 12 o'clock, within 8 inches of joint: NO - PATCH86.8 ft. SZ - Surface Other, at 12 o'clock, within 8 inches of joint: NO - PATCH116.8 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 4" - Open139.1 ft. SZ - Surface Other, at 11 o'clock, within 8 inches of joint: NO - ROUGH SPOT147.6 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 4" - Open163.4 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 4" - Open199.6 ft. SZ - Surface Other, at 09 o'clock, within 8 inches of joint: NO - PATCH205 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"205.7 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 4" - Open223.7 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 4" - Open241 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4" - Open243.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"243.6 ft. RFC - Roots Fine Connection, at 02 o'clock, within 8 inches of joint: NO - SLIGHT282.6 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 4"299.8 ft. LFZ - Lining Failure Other, at 03 o'clock, within 8 inches of joint: YES - Cut314.4 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 4"314.4 ft. LFZ - Lining Failure Other, at 12 o'clock, within 8 inches of joint: NO - circilar cut314.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"314.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 05 o'clock, , within 8 inches of joint: YES, Finish314.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"314.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 09 o'clock, , within 8 inches of joint: YES, Finish316.1 ft. AMH - Downstream Manhole, Survey Ends - 01:35 am

Observation photos (3)

  • Surface Other, at 01 o'clock, within 8 inches of joint: NO - PATCH

    58.5 ft. - Surface Other, at 01 o'clock, within 8 inches of joint: NO - PATCH

  • Surface Other, at 11 o'clock, within 8 inches of joint: NO - ROUGH SPOT

    139.1 ft. - Surface Other, at 11 o'clock, within 8 inches of joint: NO - ROUGH SPOT

  • Lining Failure Other, at 12 o'clock, within 8 inches of joint: NO - circilar cut

    314.4 ft. - Lining Failure Other, at 12 o'clock, within 8 inches of joint: NO - circilar cut

Observations (30)

DistanceCodeObservation
147.6TFOpen
205.7TBOpen
116.8TFOpen
316.1AMH01:35 am
0MWM
205TFC
243.6TFA
0AMH12:01 AM
82.4SZPATCH
163.4TFOpen
0TF
314.4TFC
282.6TF
86.8SZPATCH
2DAGS
314.4LFZcircilar cut
314.4TFC
223.7TFOpen
199.6SZPATCH
2DAGS
58.5SZPATCH
0TFA
314.4DAGS
314.4TFC
299.8LFZCut
314.4DAGS
0MWL
243.6RFCSLIGHT
139.1SZROUGH SPOT
241TFOpen

Properties (6)

custom_field_two
3
customer
LACSD
datetime
2020-05-18T23:58:01-07:00
documentation
REVELES, OLIVER III, CASTILLO, SKINNER
is_lateral_inspection
false
lining
CIPP