Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 22, 2020, 09:04 AM
  • 04 0003_04 0002_5222020_040110.mp4

Date
05/22/2020
W/O
0823728
Weather
Dry
Operator/Surveyor
REVELES
Sewer ID
Z00408
PipeID
P11733
Time
2:04 AM
Certificate
U-115-06022630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1427
Sewer Name
04 DISTRICT #4 OUTFALL TRUNK
City
BEVERLY HILLS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 04
Page No.
03
Purpose
Routine Assessment
Project
20200522VMR_DISTRICT_4_OUTFALL_TRUNK
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
04 0003
Downstream MH
04 0002
Dir. of Survey
Downstream
Length Surveyed
374.5 ft.
Total Length
374.5 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 04 0003 to 04 0002
MH: 04 0003MH: 04 0002downstream0 ft. AMH - Upstream Manhole, Survey Begins - 03:58 AM0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 4"0 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4"9.4 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start26.8 ft. SZC - Surface Other Chemical, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - SCATTGERED MAG COAT371.5 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish371.6 ft. SZC - Surface Other Chemical, from 10 to 02 o'clock, within 8 inches of joint: NO, Finish - SCATTERED MAG COAT374.5 ft. AMH - Downstream Manhole, Survey Ends - 04:19 AM

Observations (10)

DistanceCodeObservation
0AMH03:58 AM
9.4SSS
371.5SSS
0MWL
371.6SZCSCATTERED MAG COAT
0MWM
374.5AMH04:19 AM
0TFA
0TF
26.8SZCSCATTGERED MAG COAT

Properties (6)

custom_field_three
SPALLING
custom_field_two
3
customer
LACSD
datetime
2020-05-22T02:04:57-07:00
documentation
REVELES, CASTILLO, SKINNER
is_lateral_inspection
false