Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 14, 2020, 11:33 PM
  • A 0571_A 0570 _04142020_224425.mp4

Date
04/14/2020
W/O
823816
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00327
PipeID
P08352
Time
4:33 PM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7388
Sewer Name
A JOA-1A SOUTH HAWTHORNE-WARFIELD AV EXTENSION
City
LAWNDALE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_823816_TV05327_APR2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
A 0571
Downstream MH
A 0570
Dir. of Survey
Downstream
Length Surveyed
521.5 ft.
Total Length
521.5 ft.
Structural Index
4
Structural Quick
4F32
Structural Rating
156
O&M Index
2
O&M Quick
2Z00
O&M Rating
270
Overall Index
2
Overall Quick
Overall Rating
426
Pipe schematic from manhole A 0571 to A 0570
MH: A 0571MH: A 0570downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 05710 ft. MGO - General Observation - CONNECTION AT MH 3 OCLOCK0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start7.4 ft. MGO - General Observation - SIGNS OF CLEANING DAMAGE36.8 ft. CS - Crack Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES38.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"40 ft. FM - Fracture Multiple, from 03 to 09 o'clock, within 8 inches of joint: YES43.7 ft. H - Hole, at 01 o'clock, within 8 inches of joint: YES43.7 ft. CM - Crack Multiple, from 01 to 03 o'clock, within 8 inches of joint: YES46.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"47.8 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES73.5 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES74.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"76.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start98.4 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"121.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"150.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"158 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"191.6 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"194.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"243.4 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"246.6 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"248.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish280.5 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 10"280.5 ft. RPZ - Repair Other, within 8 inches of joint: YES - MANHOLE COVERED/ABANDONED MH280.5 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 10"330.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"344.4 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"361.2 ft. DSF - Deposits Settled Fine, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start367.4 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"396.1 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"414.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"415.9 ft. CS - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES447.2 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"455.3 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"498.9 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"501.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"519 ft. DSF - Deposits Settled Fine, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Finish519 ft. MGO - General Observation - SURFACE SPALLING THROUGHOUT THE REACH519 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish521.5 ft. AMH - Downstream Manhole, Survey Ends - A 0570

Observation photos (12)

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - SIGNS OF CLEANING DAMAGE

    7.4 ft. - General Observation - SIGNS OF CLEANING DAMAGE

  • Crack Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES

    36.8 ft. - Crack Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 03 to 09 o'clock, within 8 inches of joint: YES

    40 ft. - Fracture Multiple, from 03 to 09 o'clock, within 8 inches of joint: YES

  • Hole, at 01 o'clock, within 8 inches of joint: YES

    43.7 ft. - Hole, at 01 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 01 to 03 o'clock, within 8 inches of joint: YES

    43.7 ft. - Crack Multiple, from 01 to 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    47.8 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    73.5 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    76.4 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Repair Other, within 8 inches of joint: YES - MANHOLE COVERED/ABANDONED MH

    280.5 ft. - Repair Other, within 8 inches of joint: YES - MANHOLE COVERED/ABANDONED MH

  • Deposits Settled Fine,  10 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES, Start

    361.2 ft. - Deposits Settled Fine, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start

  • Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

    415.9 ft. - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

Observations (43)

DistanceCodeObservation
73.5FM
121.8TFC
498.9TF
46.7TFC
76.4FM
280.5TFC
0MWM
191.6TFC
150.3TFC
521.5AMHA 0570
519DSF
519MGOSURFACE SPALLING THROUGHOUT THE REACH
414.3TFC
0AMHA 0571
367.4TFC
0MGOCONNECTION AT MH 3 OCLOCK
501.8TFC
43.7H
330.9TFC
194.7TFC
98.4TFC
74.8TFC
158TFC
415.9CS
280.5RPZMANHOLE COVERED/ABANDONED MH
246.6TFC
2DAGS
280.5TFC
248.2FM
47.8CL
243.4TFC
43.7CM
38.3TFC
361.2DSF
36.8CS
0MWL
40FM
344.4TFC
7.4MGOSIGNS OF CLEANING DAMAGE
519DAGS
447.2TFC
396.1TF
455.3TF

Properties (6)

additional_info
SC416507
custom_field_two
2
customer
LACSD
datetime
2020-04-14T16:33:14-07:00
documentation
PRO PIPE
is_lateral_inspection
false