Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 9, 2020, 09:05 AM
  • H 0220_H 0219 _04092020_020910.mp4

Date
04/09/2020
W/O
823763
Weather
Light Rain
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00171
PipeID
P10637
Time
2:05 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7521
Sewer Name
H JOINT OUTFALL H - UNIT 2F
City
BELL
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_823763_TV02321_APR2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
H 0220
Downstream MH
H 0219
Dir. of Survey
Downstream
Length Surveyed
11.1 ft.
Total Length
11.1 ft.
Structural Index
2
Structural Quick
2200
Structural Rating
4
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
8
Pipe schematic from manhole H 0220 to H 0219
MH: H 0220MH: H 0219downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 02200 ft. MWM - Water Mark, 15 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start8.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish8.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish11.1 ft. AMH - Downstream Manhole, Survey Ends - H 021911.1 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (2)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
11.1AMHH 0219
2SSS
2DAGS
8.4DAGS
0MWL
8.4SSS
11.1MGOCONNECTION AT MH 9 O'CLOCK
0AMHH 0220
0MWM

Properties (6)

additional_info
SC411211
custom_field_two
3
customer
LACSD
datetime
2020-04-09T02:05:19-07:00
documentation
PRO PIPE
is_lateral_inspection
false