Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 23, 2020, 09:37 AM
  • 18 0449_18 0448 _04232020_025054.mp4

Date
04/23/2020
W/O
823681
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00675
PipeID
P14300
Time
2:37 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
k7578
Sewer Name
18 FLORENCE AVENUE TRUNK
City
santa fe springs
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_823681_TV18092_APR2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0449
Downstream MH
18 0448
Dir. of Survey
Downstream
Length Surveyed
376.7 ft.
Total Length
376.7 ft.
Structural Index
3
Structural Quick
3N2N
Structural Rating
372
O&M Index
2
O&M Quick
312]
O&M Rating
303
Overall Index
2
Overall Quick
Overall Rating
675
Pipe schematic from manhole 18 0449 to 18 0448
MH: 18 0449MH: 18 0448downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 18 04492 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 12 to 12 o'clock, , within 8 inches of joint: YES, Start2.3 ft. MMC - Material Change, Vitrified clay pipe2.7 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start16.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"26.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"34.8 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES47.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"78.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"103.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"129.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"146.1 ft. TBI - Tap Break-In Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 1" - ACTIVE150.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"175.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"201.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"227.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN252.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"278.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"295.2 ft. TBD - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: YES, 4", 6" - 70% GREASE-LATERAL299 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"325 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"350.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"374 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 12 to 12 o'clock, , within 8 inches of joint: YES, Finish374 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish374 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish376.7 ft. AMH - Downstream Manhole, Survey Ends - 18 0448376.7 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (5)

  • Material Change, Vitrified clay pipe

    2.3 ft. - Material Change, Vitrified clay pipe

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    2.7 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    34.8 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Tap Break-In Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 1" - ACTIVE

    146.1 ft. - Tap Break-In Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 1" - ACTIVE

  • Tap Break-In Defective, at 02 o'clock, -,  , within 8 inches of joint: YES, 4", 6" - 70% GREASE-LATERAL

    295.2 ft. - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: YES, 4", 6" - 70% GREASE-LATERAL

Observations (32)

DistanceCodeObservation
376.7AMH18 0448
299TFC
227.4TFOPEN
374DAGS
0MWM
350.7TFC
374SAV
376.7DAE
278.7TFC
103.8TFC
78.1TFC
295.2TBD70% GREASE-LATERAL
201.6TFC
252.9TFC
26.6TFC
129.3TF
2SSS
2SAV
2DAGS
374SSS
150.1TFC
0MWL
47.2TFC
146.1TBIACTIVE
325TFC
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
2.7DAE
2.3MMC
175.8TFC
34.8CL
0AMH18 0449
16.2TFC

Properties (6)

additional_info
SC411137
custom_field_two
3
customer
LACSD
datetime
2020-04-23T02:37:10-07:00
documentation
PROPIPE
is_lateral_inspection
false