Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 15, 2020, 05:30 AM
  • 15 0366_15 0365 _04142020_224136.mp4

Date
04/14/2020
W/O
823766
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00598
PipeID
P12292
Time
10:30 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7522
Sewer Name
15 BALDWIN PARK TRUNK
City
BALDWIN PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_823766_TV15016_APR2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
15 0366
Downstream MH
15 0365
Dir. of Survey
Downstream
Length Surveyed
258.6 ft.
Total Length
258.6 ft.
Structural Index
3
Structural Quick
3I2I
Structural Rating
255
O&M Index
2
O&M Quick
2I00
O&M Rating
102
Overall Index
2
Overall Quick
Overall Rating
357
Pipe schematic from manhole 15 0366 to 15 0365
MH: 15 0366MH: 15 0365downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 15 03660 ft. MGO - General Observation - CONN @ MH 3 O' CLOCK/UNKNOWN0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/UNKNOWN2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. MGO - General Observation - 60% MAG COAT THROUGHOUT2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start73.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"77.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"126 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN130.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"167 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"207.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"212.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"253 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"256.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish256.8 ft. MGO - General Observation - COCKROACHES IN MANHOLE256.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish256.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish258.6 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE258.6 ft. AMH - Downstream Manhole, Survey Ends - 15 0365

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    256.8 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (24)

DistanceCodeObservation
207.6TFC
256.8SAP
0MWM
256.8MGOCOCKROACHES IN MANHOLE
73.1TFC
77.2TFC
2SAP
0MWL
212.2TFA
253TFC
0MGOCOCKROACHES IN MANHOLE
0AMH15 0366
126TFOPEN
2DAGS
167TFC
0MGOCONN @ MH 3 O' CLOCK/UNKNOWN
256.8SSS
2MGO60% MAG COAT THROUGHOUT
258.6MGOCONN @ MH 9 O'CLOCK/ACTIVE
0MGOCONN @ MH 9 O'CLOCK/UNKNOWN
256.8DAGS
130.5TFA
2SSS
258.6AMH15 0365

Properties (6)

additional_info
SC411213
custom_field_two
3
customer
LACSD
datetime
2020-04-14T22:30:52-07:00
documentation
PRO PIPE
is_lateral_inspection
false