Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 23, 2020, 04:22 AM
  • 02 0994_02 0993_04222020_213010.mp4

Date
04/22/2020
W/O
823888
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00279
PipeID
P03566
Time
9:22 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7536
Sewer Name
02 MONTEBELLO TRUNK
City
COMMERCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_823888_TV02334_APR2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0994
Downstream MH
02 0993
Dir. of Survey
Downstream
Length Surveyed
172.6 ft.
Total Length
172.6 ft.
Structural Index
3
Structural Quick
3F00
Structural Rating
105
O&M Index
2
O&M Quick
2F00
O&M Rating
68
Overall Index
3
Overall Quick
Overall Rating
173
Pipe schematic from manhole 02 0994 to 02 0993
MH: 02 0994MH: 02 0993downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 09942 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start15.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES107.9 ft. MGO - General Observation - ABANDONED MH168 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 4" - OPEN170.7 ft. MGO - General Observation - COCKROACHES IN MANHOLE170.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish170.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish172 ft. MGO - General Observation - SHELF CHIPPED @ MH172.6 ft. AMH - Downstream Manhole, Survey Ends - 02 0993

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    15.1 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • General Observation - ABANDONED MH

    107.9 ft. - General Observation - ABANDONED MH

  • General Observation - COCKROACHES IN MANHOLE

    170.7 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (14)

DistanceCodeObservation
170.7MGOCOCKROACHES IN MANHOLE
0MWL
172MGOSHELF CHIPPED @ MH
168TBOPEN
0MGOCOCKROACHES IN MANHOLE
172.6AMH02 0993
2DAGS
170.7DAGS
170.7CM
0MWM
2CM
15.1CM
107.9MGOABANDONED MH
0AMH02 0994

Properties (6)

additional_info
SC411227
custom_field_two
3
customer
LACSD
datetime
2020-04-22T21:22:27-07:00
documentation
PRO PIPE
is_lateral_inspection
false