Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 16, 2020, 06:57 AM
  • 01 1186_01 1185_04162020_000726.mp4

Date
04/15/2020
W/O
823818
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00225
PipeID
P02040
Time
11:57 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7570
Sewer Name
01 WILCOX AVENUE TRUNK
City
BELL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
05
Purpose
Routine Assessment
Project
RFIR_WO_823818_TV01257_APR2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 1186
Downstream MH
01 1185
Dir. of Survey
Downstream
Length Surveyed
258.2 ft.
Total Length
258.2 ft.
Structural Index
3
Structural Quick
473I
Structural Rating
184
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
184
Pipe schematic from manhole 01 1186 to 01 1185
MH: 01 1186MH: 01 1185downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 11860 ft. MWL - Water Level, 15 %of cross sectional area3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start58 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"66.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"69.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"106.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"110 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"128.8 ft. FM - Fracture Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES, Start147.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"147.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES150.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"164 ft. FM - Fracture Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES, Finish185.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"188.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"226.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"228.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"258 ft. MGO - General Observation - SURFACE SPALLING THROUGHOUT THE REACH258 ft. MGO - General Observation - SLIGHT GREASE THROUGHOUT, 4 TO 8 OCLOCK258.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish258.2 ft. AMH - Downstream Manhole, Survey Ends - 01 1185

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES, Start

    128.8 ft. - Fracture Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

    147.3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (24)

DistanceCodeObservation
69.8TF
258MGOSURFACE SPALLING THROUGHOUT THE REACH
147.3TF
0MGOCONNECTION AT MH 9 O'CLOCK
128.8FM
0MGOCONNECTION AT MH 3 O'CLOCK
164FM
3SAV
228.5TF
185.6TF
226.2TF
258.2SAV
188.5TF
258MGOSLIGHT GREASE THROUGHOUT, 4 TO 8 OCLOCK
106.9TF
0MWM
0AMH01 1186
58TF
150.4TF
147.3SAP
110TF
66.4TF
258.2AMH01 1185
0MWL

Properties (6)

additional_info
SC411129
custom_field_two
3
customer
LACSD
datetime
2020-04-15T23:57:00-07:00
documentation
PROPIPE
is_lateral_inspection
false