Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 16, 2020, 07:08 AM
  • 01 1185_01 1184_04162020_002514.mp4

Date
04/16/2020
W/O
823818
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00225
PipeID
P02039
Time
12:08 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7570
Sewer Name
01 WILCOX AVENUE TRUNK
City
BELL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
05
Purpose
Routine Assessment
Project
RFIR_WO_823818_TV01257_APR2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 1185
Downstream MH
01 1184
Dir. of Survey
Downstream
Length Surveyed
390.9 ft.
Total Length
390.9 ft.
Structural Index
3
Structural Quick
413T
Structural Rating
319
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
319
Pipe schematic from manhole 01 1185 to 01 1184
MH: 01 1185MH: 01 1184downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 11850 ft. MWL - Water Level, 15 %of cross sectional area2.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"9.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"50 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"52.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"91.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"93.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"126 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"129.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"170.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"198.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"209.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"211.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"233.2 ft. FM - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES251.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start251.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"276.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"290.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"322.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"329.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"332 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"386.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish390 ft. MGO - General Observation - SURFACE SPALLING THROUGHOUT THE REACH390.9 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK390.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish390.9 ft. AMH - Downstream Manhole, Survey Ends - 01 1184390.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

    233.2 ft. - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    251.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (30)

DistanceCodeObservation
233.2FM
390.9MGOCONNECTION AT MH 3 O'CLOCK
91.1TF
390MGOSURFACE SPALLING THROUGHOUT THE REACH
52.5TF
251.6CM
386.3CM
198.9TF
93.4TF
170.4TF
390.9SAV
50TF
6TF
0MWM
2.6SAV
0AMH01 1185
322.8TF
209.7TF
329.8TF
129.7TF
276.6TFA
390.9AMH01 1184
9.3TF
251.6TF
390.9MGOCONNECTION AT MH 9 O'CLOCK
211.6TF
290.3TF
0MWL
126TFA
332TF

Properties (6)

additional_info
SC411129
custom_field_two
3
customer
LACSD
datetime
2020-04-16T00:08:55-07:00
documentation
PROPIPE
is_lateral_inspection
false