Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 16, 2020, 06:03 AM
  • 01 0093_01 0092_04152020_231453.mp4

Date
04/15/2020
W/O
823817
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00209
PipeID
P00762
Time
11:03 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7569
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_823817_TV01254_APR2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
01 0093
Downstream MH
01 0092
Dir. of Survey
Downstream
Length Surveyed
333.1 ft.
Total Length
333.1 ft.
Structural Index
3
Structural Quick
3L2L
Structural Rating
330
O&M Index
2
O&M Quick
2M12
O&M Rating
138
Overall Index
2
Overall Quick
Overall Rating
468
Pipe schematic from manhole 01 0093 to 01 0092
MH: 01 0093MH: 01 0092downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 00930 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. VC - Vermin Cockroach, within 8 inches of joint: NO - @ MH0 ft. MWL - Water Level, 15 %of cross sectional area0.3 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0.4 ft. MGO - General Observation - CONN @ MH 7 O'CLOCK/ACTIVE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start90.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"140.7 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN209.8 ft. RFL - Roots Fine Lateral, at 02 o'clock209.8 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - 15% ROOTS-LATERAL/ACTIVE260.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"331 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish331 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish333.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish333.1 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/OPEN333.1 ft. AMH - Downstream Manhole, Survey Ends - 01 0092333.1 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
260.2TFC
333.1CM
90.5TFC
2DAGS
2SSS
209.8RFL
0.4MGOCONN @ MH 7 O'CLOCK/ACTIVE
333.1MGOCONN @ MH 9 O'CLOCK/OPEN
331SSS
0AMH01 0093
0MWM
3.1CM
0VC@ MH
333.1AMH01 0092
0MWL
0.3MGOCONN @ MH 3 O'CLOCK/ACTIVE
140.7TFDOPEN
331DAGS
333.1MGOCONN @ MH 3 O'CLOCK/ACTIVE
209.8TFD15% ROOTS-LATERAL/ACTIVE

Properties (6)

additional_info
SC411128
custom_field_two
3
customer
LACSD
datetime
2020-04-15T23:03:14-07:00
documentation
PROPIPE
is_lateral_inspection
false