Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 13, 2020, 10:17 AM
  • 15 0877_15 0876_5132020_035318.mp4

Date
05/13/2020
W/O
0823679
Weather
Dry
Operator/Surveyor
REVELES
Sewer ID
Z00599
PipeID
P12670
Time
3:17 AM
Certificate
U-115-06022630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1417
Sewer Name
15 CALIFORNIA AVENUE TRUNK
City
DUARTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
05
Purpose
Routine Assessment
Project
20200513VMR_CALIFORNIA_AVENUE_TRUNK
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
15 0877
Downstream MH
15 0876
Dir. of Survey
Downstream
Length Surveyed
442.1 ft.
Total Length
442.1 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 15 0877 to 15 0876
MH: 15 0877MH: 15 0876downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"0 ft. AMH - Upstream Manhole, Survey Begins - 03:55 am2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 08 o'clock, , within 8 inches of joint: YES, Start2.4 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - Slight10.3 ft. SZC - Surface Other Chemical, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - Mag Coat248.2 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"254.4 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 4"440.3 ft. SZC - Surface Other Chemical, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - Mac Coat440.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: YES, Finish440.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 08 o'clock, , within 8 inches of joint: YES, Finish440.3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish442.1 ft. AMH - Downstream Manhole, Survey Ends - 04:23 am

Observations (15)

DistanceCodeObservation
254.4TFC
440.3SZCMac Coat
440.3DAGS
2.4SAVSlight
440.3DAGS
0MWL
248.2TFC
0MWM
0TFC
2DAGS
10.3SZCMag Coat
442.1AMH04:23 am
0AMH03:55 am
2DAGS
440.3SAV

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2020-05-13T03:17:00-07:00
documentation
REVELES, OLIVER III, CASTILLO, SKINNER
is_lateral_inspection
false