Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 14, 2020, 09:18 AM
  • A 0555A_A 0555 _04142020_023320.mp4

Date
04/14/2020
W/O
823782
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00327
PipeID
P08336
Time
2:18 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7386
Sewer Name
A JOA-1A SOUTH HAWTHORNE-WARFIELD AV EXTENSION
City
LAWNDALE
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_823782_TV05351_APR2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
A 0555
Downstream MH
A 0555A
Dir. of Survey
Upstream
Length Surveyed
327.9 ft.
Total Length
327.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
412L
O&M Rating
134
Overall Index
2
Overall Quick
Overall Rating
134
Pipe schematic from manhole A 0555 to A 0555A
MH: A 0555MH: A 0555Aupstream0 ft. AMH - Upstream Manhole, Survey Ends - A 0555A0.1 ft. MGO - General Observation - CONNECTION AT MH 3 OCLOCK1.7 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish31.9 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"43.2 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 8"74.8 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: YES, 8"97.4 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 8"124.7 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"155.8 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"182.8 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"202.4 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"244.5 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"260 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"273.9 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"301.4 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"325.9 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start327.9 ft. AMH - Downstream Manhole, Survey Begins - A 0555327.9 ft. MWM - Water Mark, 50 %of cross sectional area327.9 ft. MWL - Water Level, 15 %of cross sectional area

Observation photos (1)

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (19)

DistanceCodeObservation
172.1TF
26.5TF
145.1TF
327.8MGOCONNECTION AT MH 3 OCLOCK
326.2DAGS
2DAGS
125.5TF
54TF
327.9AMHA 0555A
0AMHA 0555
83.4TF
203.2TF
296TF
0MWM
284.7TFA
67.9TF
0MWL
253.1TFA
230.5TFA

Properties (6)

additional_info
SC416505
custom_field_two
3
customer
LACSD
datetime
2020-04-14T02:18:37-07:00
documentation
PRO PIPE
is_lateral_inspection