Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 14, 2020, 09:51 AM
  • A 0550_A 0549 _04142020_031342.mp4

Date
04/14/2020
W/O
823782
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00327
PipeID
P08330
Time
2:51 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7386
Sewer Name
A JOA-1A SOUTH HAWTHORNE-WARFIELD AV EXTENSION
City
LAWNDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_823782_TV05351_APR2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
A 0550
Downstream MH
A 0549
Dir. of Survey
Downstream
Length Surveyed
360.1 ft.
Total Length
360.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
412M
O&M Rating
146
Overall Index
2
Overall Quick
Overall Rating
146
Pipe schematic from manhole A 0550 to A 0549
MH: A 0550MH: A 0549downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 05502 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start10 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"19.3 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"96.1 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"139.6 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"178.9 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"193.7 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"258.1 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"301.8 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"344.4 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"356.7 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish360.1 ft. AMH - Downstream Manhole, Survey Ends - A 0549

Observation photos (1)

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
301.8TF
0MWL
10TF
19.3TB
2DAGS
193.7TF
344.4TF
96.1TF
178.9TF
356.7DAGS
139.6TF
0MWM
258.1TF
360.1AMHA 0549
0AMHA 0550

Properties (6)

additional_info
SC416505
custom_field_two
3
customer
LACSD
datetime
2020-04-14T02:51:36-07:00
documentation
PRO PIPE
is_lateral_inspection
false